msel_master_relay — the MSEL solid state battery isolator

The MSEL Master Relay is a solid state battery isolator that reports over CAN. This node decodes what it says and exposes what it can be told, so its state shows up on the bus like any other signal and its settings can be changed with inspect — which matters because MSEL ship no configuration tool of their own.

cmake --build build --target msel_master_relay
./build/nodes/msel_master_relay/msel_master_relay \
    --config configs/msel_master_relay/msel_master_relay.yaml

The protocol lives in libs/msel and never touches zenoh or a CAN backend, so all of it is exercised against a stub relay with nothing plugged in:

ctest --test-dir build -L msel

That includes the send-and-wait hand-off (msel::ResponseWaiter), which is in the library rather than the node for the same reason: its interesting cases are orderings between two threads, and inside a zenoh service callback they can be reasoned about but not provoked. The one worth knowing is that an answer arriving after its caller gave up is dropped, not saved for the next command — these acknowledgements are late by nature, so handing one on would report the wrong command as accepted.

Read this before changing any setting

Every configuration command is ignored unless a human is pressing and holding the external kill switch on the relay while the frame is transmitted. There is no software substitute. A command sent without it is not rejected — it is not answered at all, which looks exactly like a node that is not running.

A settings call waits for the relay to answer and tells you what it said. ok means the relay accepted the change, not that bytes were transmitted. So the intended sequence is: hold the switch, make the call, read the reply.

A command that is never answered is therefore an ordinary outcome rather than an error, and it is reported as one — answered: false with a plain explanation. That is what an unheld switch looks like, and it is also what an unpowered, re-addressed or wrong-baud-rate relay looks like, which is why the message names all four.

What it publishes

With the default topic_prefix of nodes/msel_master_relay:

Topic Schema Notes
…/status MselMasterRelayStatus Voltage out, load current, internal temperature, warning bits, state
…/info MselMasterRelayInfo Serial number, input voltage, shutdown history
…/config MselMasterRelayConfig The relay’s stored settings, read back from its own messages
…/switch_state MselMasterRelaySwitchState Only on serial 64666 and above; absent on older units, which is normal

There is no config_response topic. The relay’s answer to a settings change is waited for by the node and returned by the call that caused it — see below.

Load current is signed: positive while the battery is discharging, negative while it is being charged. It is accurate to ±10% or 1 A, whichever is greater — a whole-system draw indication, not a per-circuit measurement.

Health

nodes/msel_master_relay/health (NodeHealth), once a second and at once on any change:

Check Not ok when
link no status frame from the relay for two seconds

inspect health prints them.

The services

Key Request Effect
…/get_settings MselGetSettingsRequest Read current settings. Takes no arguments; call with --data '{}'
…/set_base_address MselSetBaseAddressRequest Move all three messages. Live on acknowledge
…/set_transmit_rate MselSetTransmitRateRequest 10 Hz or 100 Hz. Needs a power cycle
…/set_baud_and_shutdown_delay MselSetBaudAndShutdownDelayRequest Bus rate and hold-up time. See the warning below
…/set_output_drive MselSetOutputDriveRequest PDM/ECU output drive mode. Needs a power cycle
…/set_can_shutdown MselSetCanShutdownRequest Enable remote shutdown and set its address. Needs a power cycle
…/can_kill MselCanKillRequest Isolates the battery and stops the engine. Gated — see below

Every write returns an MselCommandResponse:

Field Means
ok The relay accepted it. False covers all three failures below
answered Whether the relay said anything at all within the wait window
response / responseRaw What it said. noAnswer when it said nothing
error Why not, in the words you need: a refusal here, a rejection code, or the timeout and what usually causes it
frameSent The exact bytes that went out. Empty when nothing was sent
waitedMs How long the node waited before being answered or giving up
requiresPowerCycle, holdExternalKillSwitch Returned as data rather than logged, because the caller is the one who has to act on them
notAcknowledged Only can_kill — see below

The three ways a write fails are worth telling apart, because they need completely different things done about them:

ok: false, frameSent: ""        -> refused here. Bad value, or not permitted
ok: false, answered: false      -> sent, nothing came back. Hold the switch
ok: false, answered: true       -> the relay rejected it. `response` says why

can_kill is the exception: the relay acts on the kill frame the moment it arrives and never acknowledges it, so that call does not wait. It reports notAcknowledged: true so its answered: false is not misread as a failure at the one moment nobody should be in doubt.

How long it waits is command_timeout_ms, 1000ms by default. Your own query timeout has to be longer than the node’s or you get a transport failure instead of the answer — inspect call gives up after 2000ms unless you pass --timeout. The node refuses a configured value outside 100..10000ms for the same reason at both ends: too short and an acknowledgement that queued behind the relay’s own 10Hz telemetry reads as silence, too long and the caller gives up first.

./build/nodes/inspect/inspect services                      # discover the keys
./build/nodes/inspect/inspect schema MselSetOutputDriveRequest
./build/nodes/inspect/inspect call nodes/msel_master_relay/get_settings --data '{}'
./build/nodes/inspect/inspect call nodes/msel_master_relay/set_output_drive \
    --data '{"drive":"activeLowLowSide"}'

valid: false in a get_settings response means the relay’s info message has not been seen yet — the difference between “the shutdown delay is zero” and “we have not heard from this relay at all”.

Three things that will catch you out

Changing the baud rate can make the relay disappear. The new rate takes effect at the next power cycle. If the rest of the bus is not moved to match, the relay comes back speaking a language nothing else on the wire understands, and the only way back is a CAN interface set to the new rate. Change the bus first, or be ready to chase it.

The message identifiers are not constants. The base address is user-configurable, and the three messages sit at base, base+1 and base+3 — not base+2, which is why MSEL’s own default kill address of 0x6E6 sits in that gap. A relay that has been re-addressed is silent on 0x6E4 and looks identical to one that is unpowered. If the status topic never updates, check base_address before you check the wiring.

Changing the base address through this node retunes its decoder in place, so telemetry keeps flowing. Nothing else on the bus is told: loggers, dashes and DBC imports elsewhere will still be looking at the old identifiers.

It only retunes if the relay actually acknowledged the move, and reverts if it did not. That matters because an unacknowledged command is the common case here: without the fix, a set_base_address sent without the switch held left the node listening at an address the relay had never moved to, and telemetry stopped with nothing said about why. While the change is in flight the node listens for the acknowledgement at both addresses — the relay re-addresses as it accepts, so the answer comes back at the new one, but the manual can also be read as answering before the move. Watching both costs nothing and is right either way.

The relay stops transmitting on a quiet bus. If it sees nothing for more than two of its own transmit cycles — checked every five seconds — it disables CAN transmission until the bus is alive again, and shows a flashing green LED. A relay wired to a bus with nothing else on it will therefore go silent, and that is the device working as designed rather than a fault.

When a change takes effect

Command Live on acknowledge Needs a power cycle
Base address ✓  
Shutdown delay ✓  
Transmit rate   ✓
Baud rate   ✓
Output drive   ✓
CAN shutdown enable   ✓

Baud rate and shutdown delay travel in one command because the device packs them into one frame, so that command is reported as needing a power cycle even though half of it is immediate. That is the answer that does not mislead: cycle the relay and you get both changes, do not and you get only the delay.

Remote shutdown

The relay accepts a CAN frame that isolates the battery and stops the engine. This node can send it, and refuses to unless both gates are open:

  1. allow_can_kill: true in the node’s config, which is false by default.
  2. confirm set to exactly ISOLATE-THE-BATTERY in the request.

Neither alone is sufficient — a config file left permissive on a bench should not turn a stray service call into a way to stop a moving vehicle. The relay itself also has to have remote shutdown enabled in its own settings, which it is not from the factory, so in practice there are three.

Unlike the configuration commands, the kill frame does not need the external kill switch held. It is acted on the moment it arrives; that is the point of it.

MSEL’s own warning is worth repeating: if you drive this from a MoTeC accident data recorder, check previously logged data to make sure the severe-event threshold does not trigger on an ordinary curb strike.

Trying it without hardware

Everything below runs against a virtual CAN channel, with no relay present.

./build/nodes/msel_master_relay/msel_master_relay \
    --config configs/msel_master_relay/msel_master_relay.yaml &

./build/nodes/inspect/inspect echo nodes/msel_master_relay/status &

# 12.56 V out, 54.5 A, 25.2 C, no warnings, status "normal"
./build/nodes/inspect/inspect publish vehicle/can0/rx --schema CanFrame \
    --data '{"id":1764,"len":8,"data":[4,232,2,33,0,252,0,1]}'

# The relay's settings, from its info message
./build/nodes/inspect/inspect publish vehicle/can0/rx --schema CanFrame \
    --data '{"id":1765,"len":8,"data":[4,232,252,154,86,10,15,135]}'

To watch a command go out, subscribe to the transmit topic and make a call:

./build/nodes/inspect/inspect echo vehicle/can0/tx &
./build/nodes/inspect/inspect call nodes/msel_master_relay/set_output_drive \
    --data '{"drive":"activeLowLowSide"}'
# id 1929 (0x789), data 0A BC 06 06 00 00 0A BC -- the manual's table 20
# and, a second later: ok false, answered false -- nothing is out there to answer

You can play the relay’s half too, which is how the waiting was checked without hardware. Its answer is the same byte eight times on the base identifier, so injecting one while a call is in flight is a one-liner. Give the call a wide window, because inspect takes a moment to start:

# In one shell, with command_timeout_ms raised to 6000 in the config:
./build/nodes/inspect/inspect call nodes/msel_master_relay/set_output_drive \
    --data '{"drive":"activeLowLowSide"}' --timeout 9000

# In another, before that window closes -- 0x00 x8 is "success" on 0x6E4:
./build/nodes/inspect/inspect publish vehicle/can0/rx --schema CanFrame \
    --data '{"id":1764,"len":8,"data":[0,0,0,0,0,0,0,0]}'
# the call returns ok: true, answered: true, waitedMs: <however long you took>

# 0x33 x8 is a rejection, and comes back as response: invalidId
./build/nodes/inspect/inspect publish vehicle/can0/rx --schema CanFrame \
    --data '{"id":1764,"len":8,"data":[51,51,51,51,51,51,51,51]}'

Note the ordering trap if you script both halves: publish too early and the answer is dropped as unsolicited — correctly, since no command was outstanding — and the call still times out. The node logs the decode, so a log line that comes before the “sent” line is the giveaway.

Where the protocol description came from

dbcs/msel/msel_master_relay.dbc is authored in this repository from the Master Relay User’s Manual Rev 2.0 (September 2025), not shipped by the vendor. MSEL do publish a .dbc, but it is dated 2014-11-19 — eleven years older than that manual — and describes a device that no longer matches: no 0x6E7 message, no value tables, and signal ranges that contradict the specification.

The five configuration commands, the kill trigger and the configuration response are deliberately not in the DBC, because a DBC cannot express them. The commands are constant-magic frames on a fixed identifier carrying each value twice; the response arrives on the base status identifier, so one identifier carries two different layouts. All three live in libs/msel/include/msel/protocol.h with tests pinning them to the manual’s worked byte sequences.